1.高級別潔凈廠房空調系統宜獨立設置。所謂高級別潔凈廠房是指千級以上潔凈廠房,其原因是高級別潔凈廠房空調送風量大,如同樣面積的潔凈廠房,百級潔凈廠房的空調風量是十萬級的3.4倍,是萬級的2.25倍。另外高級別潔凈廠房的使用頻率遠低于低級別手術室,這樣無論是一個空調系統負擔多個高級別潔凈廠房,或是一個空調系統負擔一個高級別潔凈廠房和多個低級別潔凈廠房,都會使空調系統長時間處于"大馬拉小車"的運行狀態。例如一個空調系統負擔1間百級潔凈廠房和2間萬級手術室或4間十萬級潔凈廠房,只要高級別潔凈廠房不使用,則潔凈廠房設計施工系統設計風量至少大于此時所需風量的112%和84%,亦即此時系統所需風量僅為系統設計風量的47%和54.3%,而且此種因潔凈廠房使用與否引起的風量變化,不宜采用變頻調速方式進行調節,只能用調節總風閥的方式調節風量以適應系統風量變化,然而此種方式顯然不節能。所以無論從節約能源的角度,或是從使用可靠性、靈活性的角度,高級別潔凈廠房都應"按間"獨立設置空調系統,即一個凈化空調系統對應一間潔凈廠房。
 
1 high level clean room air-conditioning system should be independent set. The so-called high-level clean plant is a thousand or more clean plant, the reason is the high level of air conditioning air supply, as the sample size of the clean room, clean room air conditioning air is 3.4 times one hundred thousand times, is 2.25 times. In addition to the use of high levels of clean plant frequency is far lower than the low level operation room, so whether it is a burden on a large air-conditioning system to clean the plant, or a high level of air conditioning system to burden a high level of clean plant and a number of low-level clean plant, will make the air conditioning system long time in the running state of the big horse car. Such as an air conditioning system burden of 1 hundred grade clean workshop and 2 or one hundred thousand grade clean workshop, as long as the high level of clean plant is not used, the design and construction system design and construction system is at least 112% and 84%, which means the system is designed for the system design of 47% and 54.3%, and this is due to the use of variable frequency speed adjustment, adjustment of the total air valve to adjust the air volume to adapt to the system, but this way is not energy. Therefore, whether from the perspective of energy conservation, or from the use of reliability, flexibility, the high level of clean plant should be "according to the" independent air-conditioning system, that is, a clean air-conditioning system corresponding to a clean plant.
 
2.對于低級別潔凈廠房,盡管與高級別潔凈廠房相比空調風量小的多,但一個空調系統所負擔的潔凈廠房間數也不宜過多,因為潔凈廠房的使用情況具備不確定性。愈是高等級廠家,潔凈廠房為滿足特殊繁忙情況,設置愈多。手術室多,正常情況下的同時使用系數低,這樣當一個空調系統所負擔的潔凈廠房間數較多時,系統常處于"供大于求"的狀態,其運行能耗勢必較高,就象有的廠家所反映的"建的起,用不起"。對于低級別潔凈廠房一個空調系統所負擔的潔凈廠房不宜多于四至五間,而且一個系統負擔潔凈廠房過多,也會造成使用上的不可靠。
 
2 for the low level of clean plant, despite the high level of clean room air conditioning air is much smaller, but an air conditioning system, the burden of the clean room number also should not be too much, because the use of clean plant with uncertainty. The more high grade manufacturers, clean workshop to meet the special busy, set the. Operation room, normal circumstances, while the use of low coefficient, so that when a large number of air-conditioning system burden of a large number of clean room, the system is often in a state of oversupply, the energy consumption will be higher, as some manufacturers reflect the construction of the up, can not afford". For low level cleanroom air conditioning system of the burden of clean plant should not be more than four to five, and a burden on the system clean workshop too much, caused by the use of unreliable.
 
3.中央清潔大廳、清潔走廊、高級別手術間的準備區、無菌室等應由一個單獨的空調系統負擔,目的是保證潔凈廠房外部空氣環境時時處于"臨戰"狀態,那種將以上部位空調合在低級別潔凈廠房空調系統中的做法
 
. central clean hall, corridor in the clean and high level operation between the preparation zone, sterile rooms should be a separate air conditioning system burden, the purpose of which is to ensure clean workshop outside air environment are always in the "battle" state, that will be part of the air conditioner in the low-level clean factory building air conditioning system
 
顯然不合理。因為合在一起的空調系統,或是在潔凈廠房停止使用時系統送風能耗過大,或是無法保證潔凈廠房設計施工外部氣候環境處于受控狀態。
 
Obviously unreasonable. Because of the air conditioning system, or in the clean plant to stop using the system to send wind energy consumption is too large, or can not guarantee the clean plant design and construction of the external climate environment in a controlled state.
 
潔凈廠房空調風系統的劃分原則應該是運行可靠、調節靈活、各司其責、節約能源。在潔凈廠房設計施工 http://www.jnjkjh.com/ 方面,巨康是專業的,行業內領軍品牌,值得您的信賴!
 
The principle of division of clean workshop air conditioning system should be reliable operation, flexible adjustment, each department is responsible for energy conservation. In the design and construction of clean plant, more and more professional, industry leading brands, worthy of your trust!