凈化鋁材配件-空氣過濾器的安裝應符合的規定
- 發布人:
- 發布日期:2017-04-13 17:11:47
1 手術室高效空氣過濾器經外觀檢查合格后,應立即進行安裝;
1 operation room, high efficiency air filter through the appearance inspection, should be immediately installed;
2 安裝高效過濾器的框架應平整、清潔,每臺過濾器的安裝框架的平整度偏差,不得超過1~2㎜;
2 installation and high efficiency filter framework should be smooth, clean, and every filter mounting frame flatness deviations, shall not exceed 1 ~ 2 mm;
3 過濾器安裝方向必須正確,安裝后過濾器四周和接口,應嚴密不漏;
3 filter must be installed in the direction of the right, after the installation of the filter around and interface, should be strict no leakage;
4 高效過濾器采用機械密封時,應采用氣密墊密封,其厚度為6~8㎜,并緊貼在過濾器邊框上;安裝后墊料的壓縮應均勻,壓縮率為25~50%;安裝后應進行掃描檢漏;
4, filter adopts mechanical seal, a sealing gasket, the thickness of 6-8 mm, and close to the filter frame; after installation gasket compression should be uniform, compression rate of 250%; after installation should be scans leak;
5 高效過濾器采用液壓密封時,槽架安裝水平,并不得有滲漏現象;槽內無污物和水分。槽內密封液高度宜為槽深的2/3,密封液的熔點宜高于50℃。
5 high efficiency filter adopts hydraulic seal, the slot bracket installation level, and can not have leakage phenomenon; the groove without dirt and moisture. The height of sealing fluid in the tank should be 2/3, and the melting point of the sealing fluid should be higher than 50.
- 上一篇:潔凈廠房設計施工的可維修原則
- 下一篇:防火是潔凈廠房設計施工的重要特點