余壓閥在使用過程中存在哪些問題

發布人:
發布日期:2017-04-14 09:10:43
目前余壓閥的結構一般包括閥板、調節重錘、過濾網等幾個部分,工作時,閥板開啟一定角度,讓一定量的氣流通過。重錘在不同位置,閥板所受壓力不同,相同室內壓力下,閥板的開啟度不同,可起到調節作用。
 
The residual pressure valve structure generally consists of several parts of the valve plate, adjust the hammer, filters, and other, the work, the valve plate open a certain angle, make a certain amount of airflow through. The hammer in different position, the valve plate is subjected to different pressure, under the same indoor pressure, valve plate open degree different to regulatory role.
 
目前余壓閥安裝簡單,靈敏度高,因此使用很廣泛,但是,在使用中存在以下問題。
 
At present, the residual pressure valve is simple, high sensitivity, so it is widely used, but in the use of the following problems.
 
1 外形尺寸所造成的問題
 
1 the problem caused by the shape size
 
因為現有余壓閥的工作機制是室內壓力推開閥板進行泄壓,因此,閥板和調節重錘部分突出墻面。通常,余壓閥被要求安裝在潔凈室的下風側墻壁上,因此,突出部分便成為人流或物流的障礙。也正因為如此,很多工程實施時,將余壓閥按裝在潔凈室墻壁上方,以避免此類不便,這樣,造成了潔凈室氣流組織上的不合理。
 
Because the existing residual pressure valve the working mechanism is indoor pressure open valve plate for pressure relief. Therefore, the valve plate and regulation weight portion protruding wall. Usually residual pressure valve is installed in the clean room of the leeward side walls. Therefore, prominent part has become obstacles to abortion or logistics. Also because of this, many projects are implemented, will be installed on the wall of the remaining pressure in the clean room, to avoid this inconvenience, so that caused a clean room air flow organization unreasonable.
 
2 不可精準度量及調整
 
2 can not be accurate measurement and adjustment
 
現有余壓閥雖然具有調節部分,但是,在實際使用時,并不能將調節重錘的某個位置和房間的正壓值對應起來。重錘位置的調整和房間壓力的變化,都會引起閥板開度變化,但并不能就此簡單標定重錘位置和房間壓力的關系。在實際應用中,還牽涉到同一個潔凈空間使用什么規格及多少數量余壓閥的問題。同一個潔凈空間,在同樣的正壓情況下,使用一個余壓閥和使用多個同規格余壓閥,閥板的開度是不同的。
 
Existing residual pressure valve, although is regulated, in part, however, in actual use, will not adjust the hammer of a location and the room of the positive pressure values correspond. Heavy hammer position adjustment and room pressure changes, will lead to valve plate opening degree of change, but it is not this simple calibration of the relationship between the position of the hammer and room pressure. In practical application, it also involves the use of the same clean space and the number of the number of remaining pressure valve. The same clean space, in the same positive pressure, the use of a residual pressure valve and the use of multiple with the same specifications than the pressure valve, the valve plate is different.
 
因此,使用余壓閥的潔凈室的管理者會有一些困惑:現在余壓閥的調節是不是最佳狀態呢?現在余壓閥板開度很大,房間壓力是不是過大了呢?或者現在余壓閥閥板開度很小,房間壓力是不是需要調大呢?應該調節余壓閥的重錘還是調節回風閥呢?
 
Therefore, the use of residual pressure valve of the clean room management will be a number of confusion: now more than the adjustment of the valve is not the best state of it? Now more than a large pressure valve plate, room pressure is not too big? Or now more than the valve plate opening is very small, the room pressure is not required to adjust it? We should adjust the residual pressure valve of the hammer or adjusting the air return valve?
 
3 噪音問題
 
3 noise problem
 
現有余壓閥還存在噪音問題,在房間壓力出現大的波動時(開門瞬間等) ,閥板快速關閉,會產生比較大的噪音,有些型號的余壓閥在關閉部位貼了密封膠條,一定程度上可以降低噪音。
 
Existing pressure valve is still a noise problem, the room pressure in a large fluctuations (open door, etc.), the valve plate is quickly closed, will produce a relatively large noise, some types of excess pressure valve in the closed parts of the sealing tape, to a certain extent can reduce noise.